CRYSTALLIZER VALVE — WIRING & TROUBLESHOOTING
REF-03-A
// WIRING — CRYSTALLIZER FILL VALVE (TYPICAL)
PLC PANEL
DO Card — Ch.1
120VAC OUTPUT
120V L1
COM
DI Card — Ch.1,2
ZSO
ZSC
COM
120VAC L1 → SOL
ZSO
ZSC
SOLENOID
120VAC / 1500–3000Ω
T1 (L1)
T2
LED
AIR
ACTUATOR
Spring-return
Pneumatic
VALVE BODY
DISC / PLUG
WESTLOCK
Cam-operated
120V L1
T3→ZSO
COM
T4→ZSC
cam
ZSO → PLC DI
ZSC → PLC DI
// WIRE COLOR KEY
+120VAC L1 (hot)
Neutral (N) return
ZSO — Open confirm
ZSC — Closed confirm
Pneumatic air supply
// FAULT DIAGNOSIS — WIRING & LIMIT SWITCHES
FAULT: Commanded OPEN — PLC still shows CLOSED
① Check solenoid LED — lit? If NO → 120VAC not reaching solenoid
② Measure VAC at T1-T2 of solenoid — should read 120VAC when ON
③ If solenoid lit but valve not moving → check air supply PSI
④ If valve moved but ZSO dark → Westlock cam slipped or switch dead
FAULT: Valve is OPEN but PLC shows CLOSED
① Physically verify valve is open (stem position, check flow)
② ZSO not reaching PLC — measure voltage at DI card input terminal
③ If 0V → broken wire, or cam not reaching ZSO switch actuator
FAULT: Both ZSO and ZSC showing ON at same time
① Impossible in normal operation — one must always be OFF
② Likely: 120VAC backfeed through failed relay contact or wiring fault
③ Disconnect wires one at a time to isolate the short path
FAULT: Solenoid coil overheating / burned out
① Measure coil resistance — normal: 1500–3000Ω / shorted: <10Ω / open: ∞
② Coil rating: 120VAC for all crystallizer solenoids — never swap with 24VDC coil
③ Check duty cycle — continuous vs intermittent rating
// FAST TEST PROCEDURE
STEP 1 Force PLC DO ON → confirm solenoid LED lights
STEP 2 Measure VDC T1-T2 → should read 120VAC
STEP 3 Push manual override → does valve move? (mech vs elec isolation)
STEP 4 Check PSI at actuator port → rises when solenoid energizes
STEP 5 Manually trigger Westlock cam → ZSO/ZSC change in PLC?
// EXPECTED SIGNAL STATES BY VALVE CONDITION
VALVE STATE
PLC DO OUTPUT
SOLENOID LED
ZSO (OPEN)
ZSC (CLOSED)
AIR PSI
FULLY CLOSED
OFF (0V)
OFF
OFF (0V)
ON (120VAC)
0 PSI
FULLY OPEN
ON (120VAC)
ON
ON (120VAC)
OFF (0V)
20–30 PSI
MID-TRAVEL
ON (120VAC)
ON
OFF
OFF
rising
// INSTRUMENTATION FIELD MANUAL — CH.03 CRYSTALLIZER VALVE
03_Crystallizer_Valve/Crystallizer_Wiring_Troubleshooting.svg