CRYSTALLIZER VALVE SYSTEM — QUICK REFERENCE
REF-03-B
01
FILL VALVE
SPRING-RETURN
FAIL CLOSED
ATO — Air-to-Open
ZSO + ZSC feedback
Butterfly type
Controls dextrose IN
120VAC solenoid
Lose air = closes
02
DROP VALVE
GATE
DOUBLE-ACTING
AIR BOTH WAYS
Port A=open B=close
5/2 solenoid valve
No fail-safe position
Controls crystals OUT
Load cell mounted below
03
DIVERT VALVE
3W
3-WAY VALVE
ROUTE A or B
De-energized = Path A
Energized = Path B
Spring-return actuator
Routes dextrose flow
Rotary actuator type
05
CONTROL VALVE
I/P
MODULATING
4-20mA CONTROL
I/P positioner
3-15 PSI output
Feedback linkage
Controls flow rate
Globe or butterfly body
04
ISOLATION
MANUAL BALL VALVE
LOTO CAPABLE
Full open in operation
Close + lock for maint
NEVER bypass LOTO
Flanged, removable
Quarterly cycle check
// QUICK FIELD FACTS
AIR PRESSURES
Supply to solenoids
80–120 PSI
Minimum to operate
20 PSI
Positioner range
3–15 PSI
Normal supply
30 PSI
ELECTRICAL
Solenoid supply
120VAC
Good coil resistance
85–120 Ω
Shorted coil
under 10 Ω
Open/burned coil
infinite Ω
DISCRETE SIGNALS
ZSO — valve OPEN
120VAC ON
ZSC — valve CLOSED
120VAC ON
Mid-travel both
Both OFF
Both ON same time
WIRING FAULT
WESTLOCK CAM
Type
1700 Series
Switch type
SPDT micro
To adjust cam
Loosen set screw
Most common fault
Cam slipped on stem
PLANT
Process temp
70–80°C
Cycle time
~2 hrs
Fouling risk
HIGH
Clean interval
Monthly
// FAULT LOOKUP — SYMPTOM → FIRST CHECK
SYMPTOM
MOST LIKELY CAUSE
FIRST CHECK
Sequence stuck at valve step
ZSO or ZSC not confirming
Watch HMI DI — check Westlock cam
Valve won't open at all
No 120VAC to solenoid or no air
Solenoid LED lit? Then check air PSI
Product dripping from discharge valve
Worn gate seal or buildup
Inspect sealing face, replace gasket
Control valve hunting or oscillating
Positioner gain or linkage loose
Recalibrate positioner, check linkage
Fill valve won't close end of cycle
Spring worn or product in packing
Manual override test, check spring
Solenoid clicking, valve not switching
Low air pressure or fouled spool
Check supply PSI at valve body port
All crystallizer valves same fault
Air header pressure drop
Check main air header gauge first
Solenoid coil very hot or burned
Shorted coil or wrong voltage
Ohm test — under 10Ω = short, replace
Both ZSO and ZSC showing ON
Wiring short or backfeed
Disconnect wires one at a time to isolate
// INSTRUMENTATION FIELD MANUAL — CH.03 CRYSTALLIZER VALVE