Loop Diagnostics Calculator
// NAMUR NE43 decoder · Loop resistance calculator · mA converter · If X see Y
| mA Range | NAMUR NE43 Zone | What It Means | First Check |
|---|---|---|---|
| <3.6 mA | High failure — downscale burnout | Device fault — sensor or electronics failure. Transmitter configured for downscale burnout. | Check sensor — likely open or severely damaged. Check burnout configuration. |
| 3.6–3.9 mA | Underrange / sensor failure warning | Sensor failed low, or process genuinely below calibrated zero. Distinct from a valid 4.0 mA live zero. | Verify actual process. Check sensor connection. HART diagnostic read. |
| 3.9–4.0 mA | Approaching live zero | Process near minimum range, or slight zero drift. Watch for 3.8 mA HART alarm. | Verify process condition. Check zero calibration. |
| 4.0–20.0 mA | Valid measurement range | Normal operation. Live zero (4mA) = minimum, 20mA = maximum of calibrated span. | Calculate % span: (mA−4)÷16×100 |
| 20.0–20.5 mA | Overrange — process high | Process exceeded calibrated range. May be genuine or indicates re-ranging needed. | Verify actual process against independent measurement. |
| 20.5–21.5 mA | High overrange / saturation | Process well beyond range OR loading issue (loop resistance too high). Transmitter running out of headroom. | Calculate loop resistance. Verify supply voltage AT transmitter terminals. |
| >21.5 mA | High failure — upscale burnout | Device fault with upscale burnout configuration. Critical failure indication. | Check sensor — likely short or overpressure. Transmitter may need replacement. |
| 0 mA | Open circuit — complete loop failure | No current flowing at all. Loop is broken somewhere. | Power first: fuse → supply → wiring → transmitter power terminals. |
// THE FORMULA: R_max = (V_supply − V_min_transmitter) ÷ 0.020
Loop Resistance Calculator
Supply voltage
VDC
Min transmitter voltage
(12V = HART standard)
(12V = HART standard)
VDC
Wire resistance
(18AWG ≈ 6.5Ω/1000ft)
(18AWG ≈ 6.5Ω/1000ft)
Ω
IS barrier resistance
(0 if no barrier)
(0 if no barrier)
Ω
PLC input burden
(250Ω for 1-5V input)
(250Ω for 1-5V input)
Ω
// RESULT
600 Ω
Maximum allowable loop resistance for this supply voltage.
HART Minimum Check
HART communication requires 250–1100Ω loop resistance and minimum 12VDC at transmitter terminals.
If HART won't communicate, first check:
If HART won't communicate, first check:
Loop resistance <250Ω? → Add 250Ω resistor
Voltage at TX <12V? → Reduce resistance or increase supply
AC noise >0.2Vpp? → Ground loop or EMI — fix shielding
Wrong device address? → Check HART address config
Wire Resistance Quick Ref
| AWG | Ω per 1000ft | Notes |
|---|---|---|
| 14 AWG | 2.5 | Long runs |
| 16 AWG | 4.0 | Common field wire |
| 18 AWG | 6.5 | Most common instrument |
| 20 AWG | 10.2 | Watch on long runs |
| 22 AWG | 16.1 | Short runs only |
* Total loop = 2× cable length (out and return)
// DRAG THE SLIDER — SEE WHAT THAT mA VALUE MEANS
0 mA4 mA12 mA20 mA22 mA
12.0
mA READING
50.0%
% OF SPAN
VALID
NAMUR ZONE
Mid-range — process at 50% of calibrated span
MEANING
Normal operation. Calculate process value: (mA − 4) ÷ 16 × span + LRV
// QUICK CONVERSION FORMULAS
mA → PERCENT
% = (mA − 4) ÷ 16 × 100
8mA → (8−4)÷16×100 = 25%
12mA → 50% · 16mA → 75%
12mA → 50% · 16mA → 75%
PERCENT → mA
mA = (% ÷ 100 × 16) + 4
25% → 8mA · 50% → 12mA
75% → 16mA · 100% → 20mA
75% → 16mA · 100% → 20mA
mA → PROCESS VALUE
PV = ((mA−4)÷16) × span + LRV
0-100 PSI, 12mA → 50 PSI
0-10ft, 16mA → 7.5ft
0-10ft, 16mA → 7.5ft
mA → VOLTAGE (250Ω LOAD)
V = mA × 0.250
4mA → 1.0V · 12mA → 3.0V
20mA → 5.0V (standard 1-5V range)
20mA → 5.0V (standard 1-5V range)
// PATTERN RECOGNITION — IF YOU SEE THIS, START LOOKING HERE