Loop Diagnostics + Calculator
โ† FIELD MANUAL

Loop Diagnostics + Calculator

// NAMUR NE43 decoder ยท Loop resistance calculator ยท mA converter ยท If X see Y
// NAMUR NE43 โ€” CLICK ANY ZONE TO SEE WHAT IT MEANS
FAIL
WARN
VALID MEASUREMENT โ€” 4.0 to 20.0 mA
OVER
FAIL
Click any zone on the bar above to see what that reading means and what to check.
mA RangeNAMUR NE43 ZoneWhat It MeansFirst Check
<3.6 mAHigh failure โ€” downscale burnoutDevice fault โ€” sensor or electronics failure. Transmitter configured for downscale burnout.Check sensor โ€” likely open or severely damaged. Check burnout configuration.
3.6โ€“3.9 mAUnderrange / sensor failure warningSensor failed low, or process genuinely below calibrated zero. Distinct from a valid 4.0 mA live zero.Verify actual process. Check sensor connection. HART diagnostic read.
3.9โ€“4.0 mAApproaching live zeroProcess near minimum range, or slight zero drift. Watch for 3.8 mA HART alarm.Verify process condition. Check zero calibration.
4.0โ€“20.0 mAValid measurement rangeNormal operation. Live zero (4mA) = minimum, 20mA = maximum of calibrated span.Calculate % span: (mAโˆ’4)รท16ร—100
20.0โ€“20.5 mAOverrange โ€” process highProcess exceeded calibrated range. May be genuine or indicates re-ranging needed.Verify actual process against independent measurement.
20.5โ€“21.5 mAHigh overrange / saturationProcess well beyond range OR loading issue (loop resistance too high). Transmitter running out of headroom.Calculate loop resistance. Verify supply voltage AT transmitter terminals.
>21.5 mAHigh failure โ€” upscale burnoutDevice fault with upscale burnout configuration. Critical failure indication.Check sensor โ€” likely short or overpressure. Transmitter may need replacement.
0 mAOpen circuit โ€” complete loop failureNo current flowing at all. Loop is broken somewhere.Power first: fuse โ†’ supply โ†’ wiring โ†’ transmitter power terminals.
// THE FORMULA: R_max = (V_supply โˆ’ V_min_transmitter) รท 0.020
Loop Resistance Calculator
Supply voltage
VDC
Min transmitter voltage
(12V = HART standard)
VDC
Wire resistance
(18AWG โ‰ˆ 6.5ฮฉ/1000ft)
ฮฉ
IS barrier resistance
(0 if no barrier)
ฮฉ
PLC input burden
(250ฮฉ for 1-5V input)
ฮฉ
// RESULT
600 ฮฉ
Maximum allowable loop resistance for this supply voltage.
HART Minimum Check
HART communication requires 250โ€“1100ฮฉ loop resistance and minimum 12VDC at transmitter terminals.

If HART won't communicate, first check:
Loop resistance <250ฮฉ? โ†’ Add 250ฮฉ resistor
Voltage at TX <12V? โ†’ Reduce resistance or increase supply
AC noise >0.2Vpp? โ†’ Ground loop or EMI โ€” fix shielding
Wrong device address? โ†’ Check HART address config
Wire Resistance Quick Ref
AWG ฮฉ per 1000ft Notes
14 AWG2.5Long runs
16 AWG4.0Common field wire
18 AWG6.5Most common instrument
20 AWG10.2Watch on long runs
22 AWG16.1Short runs only
* Total loop = 2ร— cable length (out and return)
// DRAG THE SLIDER โ€” SEE WHAT THAT mA VALUE MEANS
0 mA4 mA12 mA20 mA22 mA
12.0
mA READING
50.0%
% OF SPAN
VALID
NAMUR ZONE
Mid-range โ€” process at 50% of calibrated span
MEANING
Normal operation. Calculate process value: (mA โˆ’ 4) รท 16 ร— span + LRV
// QUICK CONVERSION FORMULAS
mA โ†’ PERCENT
% = (mA โˆ’ 4) รท 16 ร— 100
8mA โ†’ (8โˆ’4)รท16ร—100 = 25%
12mA โ†’ 50% ยท 16mA โ†’ 75%
PERCENT โ†’ mA
mA = (% รท 100 ร— 16) + 4
25% โ†’ 8mA ยท 50% โ†’ 12mA
75% โ†’ 16mA ยท 100% โ†’ 20mA
mA โ†’ PROCESS VALUE
PV = ((mAโˆ’4)รท16) ร— span + LRV
0-100 PSI, 12mA โ†’ 50 PSI
0-10ft, 16mA โ†’ 7.5ft
mA โ†’ VOLTAGE (250ฮฉ LOAD)
V = mA ร— 0.250
4mA โ†’ 1.0V ยท 12mA โ†’ 3.0V
20mA โ†’ 5.0V (standard 1-5V range)
// PATTERN RECOGNITION โ€” IF YOU SEE THIS, START LOOKING HERE
If You See... First Consider...
0 mAPower first. Check fuse โ†’ check polarity โ†’ measure voltage AT transmitter terminals (not just supply) โ†’ look for broken wire. 35% of dead transmitters are power issues.
Fixed 4 mA, process activeVerify not in test mode. HART communicator check โ†’ apply known input with calibrator โ†’ compare to independent measurement. May be genuine zero โ€” confirm process state.
3.6โ€“3.9 mASensor failure low or underrange. Distinct from valid 4mA live zero. Check sensor connection, read HART diagnostics. Not a power issue.
Fixed 20 mA, normal processLoading or overrange. Calculate loop resistance โ€” R_max = (Vsupplyโˆ’12)รท0.020. Measure voltage at transmitter at full output. If voltage <12V, loop resistance is the issue.
>21.5 mAUpscale burnout โ€” device fault. Sensor shorted or overpressure damaged. Check sensor resistance. Transmitter may need replacement.
Noisy, fluctuating at 50/60 HzGround loop or power line coupling. Measure shield voltage to ground โ€” should be near 0V. Verify single-point shield grounding. Only ground at one end.
Noisy at VFD frequencies (kHz)EMI from VFD. Check cable routing โ€” minimum 12 inches separation from VFD cables. Add ferrite suppressors. Improve shield grounding.
Non-linear โ€” error increases at high endLoading confirmed. Measure voltage at transmitter terminals at full 20mA output. Should be >12VDC. If not โ€” reduce loop resistance.
HART communicates but analog wrongOutput circuit fault. Transmitter may be in digital/multidrop mode, analog output failed, or forced output active. HART communicator to check output mode.
Signal good, process value wrongCalibration or configuration. LRV/URV settings, square root extraction mode, engineering unit scaling. Not a hardware fault.
Multiple transmitters fail simultaneouslyCommon supply issue. One fuse, one supply rail, one breaker. In a parallel supply arrangement, individual failures are independent โ€” simultaneous failure points to shared supply element.
Drift after pressure spikesZero shift from overpressure. Check if sensor was exposed to pressure beyond URL. Zero trim may restore it โ€” if not, sensor damaged.
โ† Electrical Fundamentals // CH.06 CALIBRATION & ELECTRICAL Field Reference Pack โ†’