• Verify process is safe to work on
• Check if transmitter is in a critical loop
• Get operator permission before starting
• Have spare transmitter ready if needed
Step 1: Equipment Setup & Initial Checks
What you need:
Fluke 754 with fresh batteries
Test leads (red/black/blue/white)
HART cable (if HART communication needed)
Small flathead screwdriver
Multimeter backup
FLUKE
754
MEASURE
---
---
SOURCE
---
---
Initial Checks:
Power ON Fluke 754
Check battery level (should be >50%)
Press SETUP → verify units are set to °F and mA
Locate Rosemount 3144P transmitter
Check nameplate: verify it's configured for PT100 RTD
Step 2: Identify Transmitter Terminals
Terminal Block Close-Up View
1
RTD+
2
RTD-
3
RTD+
4
RTD-
5
SHIELD
6
+24V
7
COM
8
4mA+
9
4mA-
10
TEST
RTD Connections: Term 1 & 3: RTD+ (Red leads) | Term 2 & 4: RTD- (White leads)
Output/Power: Term 6: +24VDC Supply | Term 7: Common (0V) | Term 8: 4-20mA Output + | Term 9: 4-20mA Output -
💡 Common Wiring Issues
The reason your leads "sometimes need to be switched" is usually:
RTD polarity: PT100 is non-polarized, but 4-wire needs proper pairing
3-up/3-down confusion: Check if terminals 1&3 are actually connected to same RTD lead
Loop power vs self-power: Depends on how plant wiring is set up
Step 3: Connect Fluke 754 for Calibration
CONNECTION METHOD 1: Using Loop Power (Most Common — Use This First)
Turn OFF plant power to transmitter (if safe to do so)
Remove existing wires from terminals 8 & 9 (mark them!)
Connect RED lead to terminal 8 (+)
Connect BLACK lead to terminal 9 (-)
Connect BLUE lead to terminals 1&3 (RTD+)
Connect WHITE lead to terminals 2&4 (RTD-)
Turn plant power back ON
Step 4: Configure Fluke 754 Split Screen
Set up MEASURE side (left):
Press MEASURE button
Press TEMP → RTD → PT100
Verify display shows temperature in °F
Set up SOURCE side (right):
Press SOURCE button
Press mA
Press LOOP PWR (provides 24V to transmitter)
FLUKE
754
MEASURE
RTD °F
72.5
SOURCE
mA LOOP
4.00
⚠️ Troubleshooting Connection Issues
If you see "OPEN" or "---" on MEASURE side:
Check RTD connections are tight
Verify you're connected to correct terminals (1&3, 2&4)
Try swapping BLUE and WHITE leads
Use ohmmeter to check RTD resistance (should be ~110Ω at room temp)
If SOURCE side shows error or won't source:
Check if transmitter needs external 24V (some installations)
Verify loop connections (RED to +, BLACK to -)
Check if transmitter is drawing current (should see ~24mA total)
Alternative: Use External Loop Power
If LOOP PWR doesn't work: Connect plant 24V to Term 6 (+) and Term 7 (-). Set SOURCE to mA (not LOOP PWR). Measure current between RED and BLACK leads.
Step 5: Zero Point Calibration (4mA = 50°F)
On SOURCE side, set output to 4.00 mA
Wait 30 seconds for stabilization
On MEASURE side, it should read close to 50.0°F
If reading is off by more than ±2°F, transmitter needs adjustment
FLUKE
754 — ZERO POINT CHECK
MEASURE
RTD °F
50.0
SOURCE
mA LOOP
4.00
To adjust zero point (if needed):
Access transmitter configuration via HART or local adjustment
Most Rosemount units: Look for "Zero Trim" or "LRV Trim"
Adjust until MEASURE reads exactly 50.0°F
Step 6: Span Calibration (20mA = 300°F)
On SOURCE side, set output to 20.00 mA
Wait 30 seconds for stabilization
On MEASURE side, it should read close to 300.0°F
If reading is off by more than ±2°F, transmitter needs span adjustment
FLUKE
754 — SPAN CHECK
MEASURE
RTD °F
300.0
SOURCE
mA LOOP
20.00
To adjust span (if needed):
Access "Span Trim" or "URV Trim" in transmitter
Adjust until MEASURE reads exactly 300.0°F
May need to re-check zero after span adjustment
Step 7: Verify Linearity (25 / 50 / 75%)
Test at 25%, 50%, and 75% of span to verify transmitter linearity:
Test Point
Source (mA)
Expected Temp (°F)
Tolerance
0% (Zero)
4.00
50.0
±1.0°F
25%
8.00
112.5
±1.0°F
50%
12.00
175.0
±1.0°F
75%
16.00
237.5
±1.0°F
100% (Span)
20.00
300.0
±1.0°F
Record your readings:
If all points are within tolerance: Calibration PASSED
If linearity is off: Check RTD sensor or transmitter internal calibration
🔧 Common Problems & Solutions
Problem: Measure side shows "OPEN" or unstable
Check RTD connections — terminals 1&3 should be tied together, 2&4 tied together
Verify RTD resistance with ohmmeter (~110Ω at room temp)
Check for moisture in terminal block
Try different test leads
Problem: Can't source current or get power error
Check if transmitter needs external power supply
Verify loop resistance isn't too high (<600Ω typical)
Try using external 24VDC supply instead of LOOP PWR
Check fuses in transmitter or loop
Problem: Reading is way off but stable
Verify transmitter range configuration (should be 50–300°F)
Check if RTD type is correct (PT100 vs PT1000)
Confirm 4-wire vs 3-wire RTD configuration
Check for configuration errors in transmitter
Problem: Reading drifts or is noisy
Check all connections are tight
Look for EMI sources nearby (VFDs, motors)
Verify grounding is correct
Check RTD extension wire integrity
Step 8: Return to Service
Set SOURCE to 0.00 mA and turn OFF
Disconnect Fluke 754 test leads
Reconnect original plant wiring to terminals 8 & 9
Verify transmitter output matches process temperature
Document calibration results
Update calibration records/tags
💡 Pro Tips
Always check twice: Measure RTD resistance before and after
Temperature matters: Ambient changes affect calibration
Document everything: Record as-found and as-left values
Know your limits: If transmitter won't calibrate, replace it
Safety first: Some processes can't be taken offline for calibration
CALIBRATION FREQUENCY: Typically every 12 months or per plant procedures ACCURACY SPEC: Rosemount 3144P typically ±0.075% of span RESPONSE TIME: <5 seconds to 90% of step change